Cable Sizing Chart

Use this chart to pick the right cable size for a borehole, submersible or booster pump. Find your motor size (kW or HP) in the left column, then read across: each figure is the maximum cable length in metres for that cable size (mm²) before voltage drop becomes a problem. If your cable run is longer than the figure shown, move up to the next cable size.

230V single-phase pump cable sizing chart

Maximum cable length (m) by cable size – 230V single-phase motors
Motor HPMotor kW1.5 mm²2.5 mm²4 mm²6 mm²10 mm²16 mm²25 mm²35 mm²50 mm²
0.330.2517028045067011301750264035904940
0.50.371202003204808101260190025903580
0.750.5580130220320550850129017602430
10.7560100170250430670101013801910
1.51.140701201803004707109601360
21.53060901302303605507601060
32.220406090150230350490680

380V three-phase pump cable sizing chart

Maximum cable length (m) by cable size – 380V three-phase motors
Motor HPMotor kW1.5 mm²2.5 mm²4 mm²6 mm²10 mm²16 mm²25 mm²35 mm²50 mm²
0.50.3781013502160324055008530–––
0.750.5555092014802230378058608890––
10.75410680109016402780433065709010–
1.51.1300500810121020603200485066409220
21.522037059088015002340356048906380
32.215025040060010301600244033504680
53.790150240370630980149020502870
7.55.560110170260440690106014502030
107.5508013020034053081011101560
1511–50901302303605507501060
2015––70100170270410570800
2518.5–––80140210330450630
3022–––70120180280380540
4030––––90130210280400
5037–––––110170230320

A dash (–) means that combination isn’t listed – the cable is either too small for the motor or bigger than you would ever need. Figures are a guide only; always check against the pump manufacturer’s installation manual and SANS 10142 wiring rules. Not sure which cable or pump you need? Ask us or WhatsApp 061 744 1001.

Need an electrician to install the cable?

Cable size is only part of a safe pump installation. The pump also needs its own circuit breaker in the DB board, earth leakage protection, a weatherproof isolator and the correct starter or control box. In Pretoria and Centurion, Electrician Worx can wire borehole, booster and pool pump circuits and check that your cable run matches the motor size before you switch on.

Prefer a picture? Here is the same chart as an image you can save or print.

Cable sizing chart for 230V and 380V water pumps – maximum cable length by motor kW and cable size
Swimming pool with clean water circulated by a pool pump

Quality Water Pumps & Swimming Pool Pumps